You are here

Interpretation Response #PI-77-0106


Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date: 06-27-1977

Country: US

View the Interpretation Document


Response text:

June 27, 1977
Chief, Eastern Region, MTP-50-EA Acting Director, Office of Pipeline
Safety Operations

Alternatives to Section 192.755
Your memorandum of March 21, 1977, on this subject asks two separate but related questions about
possible methods of compliance with Section 192.755, "Protecting cast-iron pipelines." This section
is applicable where an existing buried pipeline is crossed by an earth excavation or ditch or is
located in potentially unstable soil
due to an excavation being dug nearby and deeper than the gas pipeline.

Section 192.755 requires When an operator has knowledge that the support for a segment of a buried
cast-iron pipeline is disturbed:

(a) That segment of the pipeline must be protected, as necessary, against damage during the
disturbance by:

(1) Vibrations from heavy construction equipment, trains, trucks, buses, or blasting; (2)  Impact
forces by vehicles;
(3) Earth movement;

(4) Apparent future excavations near the pipeline; or
(5) Other foreseeable outside forces which may subject that segment of the pipeline to bending
stress.

(b) As soon as feasible, appropriate steps must be taken    to provide permanent protection for the
disturbed segment from damage that might result from external loads, including compliance with
applicable requirements of Sections 192.317(a), 192.319, and 192.361(b)-(d).

Following are the questions submitted and OPSO's interpretations.

Question:        If an operator cuts a cast-iron pipe in two and installs a leak clamp at a point
where the operator suspects soil settlement as a result of excavation by others, can this be
considered as a satisfactory alternative to the requirements of Section 192.755?

Interpretation:  The cutting of the pipe and installation of the coupling would possibly be of some
benefit by providing flexibility.  However, without providing other means of support, such as
compacting the soil to an equivalent compaction as the original soil, supporting with a beam to
undisturbed soil, or replacing the cast-iron pipe across the area with steel pipe extending well
into the undisturbed soil, the segment would not be protected to a degree sufficient to assure the
safety of the installation.

Question:  In the case of a leak caused by cast-iron pipe breaking in two, can the installation of
a leak clamp suffice for the requirements of Section 192.755?  Or, must the operator comply with
the requirements of Section
192.755 as well so as to protect the pipe segment that was excavated against possible subsequent
bending stress
due to soil settlement?

Interpretation:  The installation of a leak clamp would be considered as adequate leak repair but
it does not provide protection against further soil settlement.  As indicated above, measures must
be taken to stop or minimize the soil movement or some degree of resistance must be provided in the
structural strength of the piping system crossing the affected area of construction.

Many operators have adopted a standard policy of replacing cast-iron pipe in this sort of a
situation with steel pipe and taking necessary measures to protect the steel pipe.  Attached are
copies of a standard procedure that is used by one company for such construction areas.

Cesar DeLeon, MTP-1

Attachment

UNITED STATES GOVERNMENT                                                                            
 DEPARTMENT OF TRANSPORTATION
Memorandum                                                                                          
MATERIALS TRANSPORTATION BUREAU DATE:                  MAR 21 1977
TO:                      Acting Director, MTP-1

FROM:                Chief, Eastern Region, MTP-50-EA

SUBJECT:            Alternative to §192.755(?)
If an operator cuts a cast iron pipe in two and installs a leak clamp at a point where the operator
suspects soil settlement as a result of excavation by others, can this be considered as a
satisfactory alternative to the requirements of §192.755?

Likewise, in the case of a leak caused by cast iron pipe breaking in two, can the installation of a
leak clamp suffice for the requirements of §192.755? Or must the operator comply with the
requirements of §192.755 as well so as to protect the pipe segment that was excavated against
possible subsequent bending stress due to soil settlement?
Lance F. Heverly


Regulation Sections

Section Subject
§ 192.755 Protecting cast-iron pipelines